| Model | ATESS HPS50 |
| AC (Grid-connected) | |
| Apparent power | 55kVA |
| Rated power | 50kW |
| Rated voltage | 400V |
| Rated current | 72A |
| Voltage range | 360V – 440V |
| Rated frequency | 50/60Hz |
| Frequency range | 45~55/55~65Hz |
| THDI | <3% |
| PF | 0.8lagging~0.8leading |
| AC connection | 3/N/PE |
| AC input | 100kVA |
| AC (Off-Grid) | |
| Apparent power | 55kVA |
| Rated power | 50kW |
| Rated voltage | 400V |
| Rated current | 72A |
| THDU | ≤2%linear |
| Rated frequency | 50/60Hz |
| Overload capability | 110%-10 mins 120%-1 min |
| DC (Battery and PV) | |
| Max. PV open-circuit voltage | 1000V DC |
| Max. PV power | 75kWp |
| PV MPPT voltage range | 480V-800V DC |
| Battery voltage range at Max. charge power |
500V-600V |
| Battery voltage range | 352-600V |
| Max. charge power | 75kW |
| Max. discharge power | 55kW |
| Max. charge current | 150A |
| Max. discharge current | 156A |
| General Information | |
| Protection degree | IP20 |
| Noise emission | <65dB(A)@1m |
| Operating temperature | -25 °C~+55 °C |
| Cooling | Forced-air |
| Relative humidity | 0-95% non-condensing |
| Maximum altitude | 6000m (derate over 3000m) |
| Dimension (W/H/D) | 950/1860/750mm |
| Weight | 610kg |
| Build-in transformer | Yes |
| Transfer between on/off grid | Automatic≤10ms |
| Standby consumption | <30W |
| Communication | |
| Display | Touch screen |
| Communication | RS485/CAN |
| Certificate | |
| CE , MEA , PEA , AS 4777.2,EN 61000-6-4:2007+A1:2011 , EN61000-6-2:2005 , EN62109-1:2010 , EN62109-2:2011 , EN 50549-1:2019 , IEC62109.1, IEC62109.2, NRS 097-2-1:2017, G99, VDE-AR-N 4105:2018,DIN VDE V 0124-100:2020-06 |
|
Commercial & Industrial Solar, Commercial & Industrial Inverters
ATESS 50kW Hybrid Inverter 352V-600v 75kW MPPT
R164 000,00
Large capacity all-in-one hybrid inverter for commercial application, supporting up to 600kW system capacity.
Only logged in customers who have purchased this product may leave a review.